- Auto/start/stop control
- Engine cool-down timer
- Environmental sealed front face
- Emergency stop pushbutton
- Text alarm/event descriptions
- 24 Volt DC operation
- Controls:
- Generator mounted - Rear facing
- IVR includes reactive droop capability, 3-phase voltage sensing,
KVAR / PF modes, RFI suppression, min / max exciter.
- Limiter and exciter diode monitor
- Generator set packages include Caterpillar's voltage
regulator
- EMCP 4.2B
- Speed adjust
- Alarm acknowledge
- Engine cycle crank
- Load histogram feature
- Lamp test
- Digital indication for:
- Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
- RPM
- PLC functionality
- Operating hours
- Oil pressure (psi, kPa or bar)
- Coolant temperature
- DC volts
- Power factor (per phase & average)
- Volts (L-L & L-N)
- kW (per phase, average & percent)
- Amps (per phase & average)
- Frequency (Hz)
- kVA (per phase, average & percent)
- kVAr (per phase, average & percent)
- Low oil pressure - High coolant temperature
- kVAr-hr (total)
- High coolant temperature
- Warning/shutdown with common LED indication of shutdowns for:
- kW-hr (total)
- Overspeed
- Low coolant temperature
- Failure to start (overcrank)
- Emergency stop
- Over/under voltage (27 / 59)
- Generator phase sequence
- Low coolant level
- Programmable protective relaying functions:
- 6 Customer programmable digital inputs
- Over/under frequency (81 o/u)
- Reverse reactive power (kVAr) (32RV)
- Serial annunciator module data link
- Reverse power (kW) (32)
- Number of I/O varies on options selected
- Overcurrent (50 / 51)
- Cat connect
- 4 Programmable relay outputs (Form A)
- Communications:
- Customer data link (Modbus RTU)
- 1 Programmable digital outputs
- 1 Programmable relay outputs (Form C)
- Accessory module data link
- 3 Analog inputs